Zhejiang KRIPAL Electric Co., Ltd.

Zhejiang KRIPAL Electric Co., Ltd 30 years experience in manufacturing ac contactor, rotary isolator switch, industrial plug socket, molded case circuit breaker and etc

Manufacturer from China
Active Member
11 Years
Home / Products / Molded Case Circuit Breaker /

160A 4 P 50KA Molded Case Circuit Breaker , Moulded Case Circuit Breaker KEMA Certified

Contact Now
Zhejiang KRIPAL Electric Co., Ltd.
Province/State:zhejiang
Country/Region:china
Contact Person:MissJessica
Contact Now

160A 4 P 50KA Molded Case Circuit Breaker , Moulded Case Circuit Breaker KEMA Certified

Ask Latest Price
Video Channel
Brand Name :KRIPAL
Model Number :UKM32-160/4
Certification :CE, KEMA
Place of Origin :China
MOQ :100 pcs
Price :negotiable
Payment Terms :T/T, L/C
Supply Ability :50000 pcs per month
Delivery Time :15 days and depends on ordering quantity
Packaging Details :Each unit packed in a individual box
Ampere range :16,20,25,32,40,50,63,80,100,125,160
Poles available :4pole
Breaking capacity :50KA 85KA
Color :Dark
Purpose :for protection of power distribution
Trip unit :thermal adjustable
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Ics=Icu 160A 4 P 50KA Moulded Case Circuit Breaker KEMA certified

KRIPAL has the Utility Model Patent for the structure of double making & double breaking!

The UKM32 series MCCB Thermal magnetic Molded Case circuit Breakers, which are the type found in most distribution boards, incorporate both techniques with the electromagnet responding instantaneously to large surges in current (short circuits) and the bimetallic strip responding to less extreme but longer-term over-current conditions. The thermal portion of the circuit breaker provides an "inverse time" response feature, which trips the circuit breaker sooner for larger overcurrents but allows smaller overloads to persist for a longer time. On very large over-currents during a short-circuit, the magnetic element trips the circuit breaker with no intentional additional delay.

Description:

1. Thermal magnetic adjustable
2. Double making & double breaking design
3. Contacts: 85% AgCdo
4. Metal parts: Cooper
5. Plastic Parts: brand-new materials

6. High breaking capacity.

7. Bearing Rotating shaft

8. The max breaking capacity of each model is up to 150 kA
9. U-type fixed contact design
10. Don't contain any noxious substances and its manufacturing and processing are performed in

accordance with the requirements of ISO14001.

Specifications:

MCCBs for power distribution

UKM32-160

UKM32-250

UKM32-630

Frame size

160

250

630

Rated current, In

16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160

40, 50, 63, 80, 100, 125, 160, 200, 250

300, 400, 500, 630

Poles

3, 4,

3, 4,

3

Rated operational Voltage, Ue

AC (V)

690

690

690

DC (V)

500

500

500

Rated impulse withstand voltage, Uimp

8

8

8

Rated insulation voltage. Uimp

750

750

750

Rated ultimate short circuit breakering capacity, Icu

N

N

N

AC 50/60HZ

220/240V (KA)

85

100

100

380/415V (KA)

50

85

65

440/460V (KA)

50

70

65

480/500V (KA)

30

50

42

660/690V (KA)

5

8

10

DC

250V (KA)

42

65

50

2 poles in series

500V (KA)

42

65

50

Rated service breaking capacity, Ics(%Icu)

100%

100%

100%

Current-limiting Capacity:

Current limiting means the limiting increase of the short circuit current in a circuit. In a circuit protected
by the UKM32 product series, both the peak value and energy l2t of the short circuit current generated
are far less than expected.

A. U -Type fixed contact design

The pre-breaking technique may be realised by means of a unique U-Type fixed contact.
The pre-breaking technique refers to that of the electrodynamic force generated throuth the U-Type
fixed contact and that wnich occurs on moving contact system. The higher the short circuit current,
the bigger the repulsive electrodynamic forces they generate simultaneously. Prior to releasing,
the electrodynamic repulsive forces may separate the moving contact from the fixed contact, and the
equivalent resistance between these two contacts is increased by streching the electrical arc.

B. Double making & double breaking design

The current-limiting function of the pre-breaking technique is enhanced because of increase in instantaneous arc resistance and arc voltage and a fast drop in the current increase rate.
Reduces the damage and loss of equipment and the power lines caused by a short circuit current,
improves the safety, and cuts down on the cost of a secondary protection device.

FAQ:

A. How's the delivery time?
Depend on your quantity, usually within 20days after receiving deposit

B. Would you accept OEM/ODM service?

Glad to say that there is planning department, technical department and mould tooling center in our factory. For the OEM & ODM, it is ok for us if your brand, market shares are great.

C. Would you offer free sample?

Samples are freely provided and shipping costs is paid on your end usually.

D What's your guaranty time?

At least 2 years and depend the product

E What's your payment term?

T/T, L/C; other terms is negotiable after further check

Inquiry Cart 0